SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
433
2 Parameters
2.2 List of parameters
Description: Sets the gain factor for the minimum excitation current, closed-loop control.
This is active if the excitation current is below 75 % of p1642.
Dependency: Refer to: p1642
Description: Displays the output of the excitation current monitoring for separately excited synchronous motors.
Description: Sets the signal source for the individual feedback signals from the excitation.
Index: [0] = Excitation ready for switching on
[1] = Excitation ready
[2] = Excitation operational
[3] = Excitation group signal fault
[4] = Excitation group signal alarm
[5] = Not used
[6] = Not used
[7] = Excitation at the voltage limit
Dependency: Refer to: r1649
Description: Sets the monitoring time of the excitation.
After an ON command, the feedback signal must be received within this monitoring time.
Note: After the on command for the excitation (r1648.0 = 1), its feedback signal must be available at r1649.1 within this
monitoring time (BI: p1645[1]).
The same monitoring time is effective after the excitation is enabled for operation (r1648.3 = 1) up to the feedback
signal "excitation operational" (r1649.2 = 1, BI: p1645[2]).
p1643[0...n] Minimum excitation current closed-loop control gain factor / I_exc_min Kp
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_CON Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6727
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 5.00 0.40
r1644 CO: Excitation current monitoring output / I_exc_monit outp
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6727
P-Group: Closed-loop control Unit group: 6_2 Unit selection: p0505
Not for motor type: ASM, PMSM, REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1645[0...7] BI: Excitation feedback signals signal source / Exc FS S_src
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 6495
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
- - [0...6] 1
[7] 0
p1646 Excitation monitoring time / Excit t_monit
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6495
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: ASM, PMSM, REL Scaling: - Expert list: 1
Min Max Factory setting
2.0 [s] 1300.0 [s] 20.0 [s]