4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1632 List Manual (LH2), 07/2016, A5E03263479A
A07994 (F, N) Drive: motor data identification not performed
Message value: -
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: VECTOR_G
Component: None Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: The "vector control" mode has been selected and a motor data identification has still not been performed.
The alarm is initiated when changing the drive data set (see r0051) in the following cases:
- vector control is parameterized in the actual drive data set (p1300 >= 20).
and
- motor data identification has still not been performed in the actual drive data set (see r3925).
Note:
For SINAMICS G120, a check is made and an alarm is output also when exiting commissioning and when the system
powers up.
Remedy: - Perform motor data identification (see p1900).
- if required, parameterize "U/f control" (p1300 < 20).
- switch over to a drive data set, in which the conditions do not apply.
Reaction upon F: NONE (OFF2)
Acknowl. upon F: IMMEDIATELY
Reaction upon N: NONE
Acknowl. upon N: NONE
F08000 (N, A) TB: +/-15 V power supply faulted
Message value: %1
Message class: Supply voltage fault (undervoltage) (3)
Drive object: All objects
Component: Controller Extension (CX) Propagation: LOCAL
Reaction: Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: Terminal Board 30 detects an incorrect internal power supply voltage.
Fault value (r0949, interpret decimal):
0: Error when testing the monitoring circuit.
1: Fault in normal operation.
Remedy: - replace Terminal Board 30.
- replace Control Unit.
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
F08010 (N, A) TB: Analog-digital converter
Message value: -
Message class: Hardware/software error (1)
Drive object: All objects
Component: Controller Extension (CX) Propagation: LOCAL
Reaction: Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The analog/digital converter on Terminal Board 30 has not supplied any converted data.
Remedy: - check the power supply.
- replace Terminal Board 30.
Reaction upon N: NONE
Acknowl. upon N: NONE