SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1903
4 Faults and alarms
4.2 List of faults and alarms
F35896 TM DRIVE-CLiQ (CU): Inconsistent component properties
Message value: Component number: %1
Message class: Internal (DRIVE-CLiQ) communication error (12)
Drive object: B_INF, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: LOCAL
Reaction: Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Infeed: OFF2 (NONE, OFF1)
Acknowledge: IMMEDIATELY
Cause: The properties of the DRIVE-CLiQ component (Terminal Module), specified by the fault value, have changed in an
incompatible fashion with respect to the properties when booted. One cause can be, e.g. that a DRIVE-CLiQ cable or
DRIVE-CLiQ component has been replaced.
Fault value (r0949, interpret decimal):
Component number.
Remedy: - carry out a POWER ON.
- when a component is replaced, the same component type and if possible the same firmware version should be
used.
- when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the
original cables should be used (ensure compliance with the maximum cable length).
F35899 (N, A) TM: Unknown fault
Message value: New message: %1
Message class: General drive fault (19)
Drive object: B_INF, TM120, TM150, TM31, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2)
Infeed: NONE (OFF1, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: A fault has occurred on the Terminal Module that cannot be interpreted by the Control Unit firmware.
This can occur if the firmware on this component is more recent than the firmware on the Control Unit.
Fault value (r0949, interpret decimal):
Fault number.
Note:
If required, the significance of this new fault can be read about in a more recent description of the Control Unit.
Remedy: - replace the firmware on the Terminal Module by an older firmware version (r0158).
- upgrade the firmware on the Control Unit (r0018).
Reaction upon N: NONE
Acknowl. upon N: NONE
Reaction upon A: NONE
Acknowl. upon A: NONE
A35903 (F, N) TM: I2C bus error occurred
Message value: -
Message class: Hardware/software error (1)
Drive object: B_INF, TM120, TM150, TM31, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: NONE
Acknowledge: NONE
Cause: An error has occurred while accessing the internal I2C bus of the Terminal Module.
Remedy: Replace the Terminal Module.
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE