2 Parameters
2.2 List of parameters
SINAMICS G130/G150
266 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the signal source to block the master control.
Dependency: Refer to: r0807
Note: The commissioning software (drive control panel) uses the master control, for example.
Description: Displays what has the master control.
The drive can be controlled via the BICO interconnection or from external (e.g. the commissioning software).
Dependency: Refer to: p0806
Notice: The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note: Bit 0 = 0: BICO interconnection active
Bit 0 = 1: Master control for PC/AOP
The commissioning software (drive control panel) uses the master control, for example.
Description: Copies one Command Data Set (CDS) into another.
Index: [0] = Source Command Data Set
[1] = Target Command Data Set
[2] = Start copying procedure
Note: Procedure:
1. In Index 0, enter which command data set should be copied.
2. In index 1, enter the command data set that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0809[2] is automatically set to 0 when copying is completed.
p0806 BI: Inhibit master control / PcCtrl inhibit
VECTOR_G, B_INF Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r0807.0 BO: Master control active / PcCtrl active
VECTOR_G, B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Master control active Yes No 5030,
6031
p0809[0...2] Copy Command Data Set CDS / Copy CDS
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8560
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 15 0