SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
35
2 Parameters
2.2 List of parameters
43: Switching-on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
44: Switching-on inhibited - supply STO terminal w/ 24 V (hardware)
45: Switching-on inhibited - rectify fault, acknowledge fault, STO
46: Switching-on inhibited - exit commissioning mode (p0009, p0010)
60: Drive object deactivated/not operational
70: Initialization
200: Wait for booting/partial booting
250: Device signals a topology error
Dependency: Refer to: r0046
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
EP: Enable Pulses (pulse enable)
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
SS2: Safe Stop 2
STO: Safe Torque Off
Description: Operating display for the infeed.
Value: 0: Operation - everything enabled
31: Ready for switching on - precharging running (p0857)
32: Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
35: Switching-on inhibited - carry out first commissioning (p0010)
41: Switching-on inhibited - set "ON/OFF1" = "0" (p0840)
42: Switching-on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
44: Switching-on inhibited - connect 24 V to terminal EP (hardware)
45: Switching-on inhibited - remove fault cause, acknowledge fault
46: Switching-on inhibited - exit commissioning mode (p0009, p0010)
60: Infeed deactivated/not operational
70: Initialization
200: Wait for booting/partial booting
250: Device signals a topology error
Dependency: Refer to: r0046
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Note: OC: Operating condition
COMM: Commissioning
Description: Operating display for Terminal Module 120 (TM120)
Value: 0: Module in cyclic operation
40: Module not in cyclic operation
50: Alarm
60: Fault
70: Initialization
120: Module deactivated
r0002 Infeed operating display / INF op_display
B_INF Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 250 -
r0002 TM120 operating display / TM120 op_display
TM120 Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 250 -