2 Parameters
2.2 List of parameters
SINAMICS G130/G150
360 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the actual output of the Vdc controller (DC link voltage controller)
Note: The regenerative power limit p1531 is used for vector control to pre-control the Vdc_max controller. The lower the
power limit is set, the lower the correction signals of the controller when the voltage limit is reached.
Description: Sets the configuration for the bypass function.
Value: 0: Bypass deactivated
1: Bypass with synchronization and overlap
2: Bypass with synchronization without overlap
3: Bypass without synchronization
Note: If the bypass function is selected ((p1260 > 0), then when the power unit restarts after POWER OFF, the state of the
bypass switch is evaluated. This means that after the ramp-up, it is possible to directly change into the standby
mode. This is only possible for p1267 = 1 (bypass using the control signal) and if the control command after the
system has been booted is still available (p1266). This function has a higher priority than the automatic restart
function (p1210).
The "bypass" function can only be switched off again (p1260 = 0) if the bypass is not active or the bypass function
has a fault.
The corresponding function should be activated in p3800 for bypass with synchronization.
Description: Control and feedback signals of the bypass switch.
Dependency: Refer to: p2369
Note: Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder cables
should be controlled. These should be selected/dimensioned for switching under load.
r1258 CO: Vdc controller output / Vdc_ctrl output
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6220
P-Group: Functions Unit group: 6_2 Unit selection: p0505
Not for motor type: REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p1260 Bypass configuration / Bypass config
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
r1261.0...11 CO/BO: Bypass control/status word / Bypass STW / ZSW
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Command switch motor - power unit Close Open -
01 Command switch motor - line supply Close Open -
02 Synchronization requested Yes No -
03 Staging status Active Not active -
05 Feedback signal switch motor - power unit Closed Opened -
06 Feedback signal switch motor - line supply Closed Opened -
07 Bypass command (from p1266) Yes No -
08 Feedback signal synchronization completed
(from p1268)
Yes No -
09 Staging requested (from p2369) Yes No -
10 Bypass in process sequence Yes No -
11 Bypass enabled Yes No -