2 Parameters
2.2 List of parameters
SINAMICS G130/G150
362 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the cause that should initiate the bypass.
Note: The parameter only has an effect for a non-synchronized bypass.
p1267.0 = 1:
The bypass is initiated by setting a binary signal. When the command is reset, after the debypass delay time (p1263)
has expired, operation at the power unit is re-selected.
p1267.1 = 1:
When the speed threshold entered in p1265 is reached, the bypass is switched in. The system only switches back
when the speed setpoint again falls below the threshold value.
Description: Sets the signal source for the feedback signal "synchronization completed" for the bypass function.
Dependency: Refer to: r3819
Description: Sets the signal source for the feedback signal of the bypass switch.
Index: [0] = Switch motor/drive
[1] = Switch motor/line supply
Note: In the case of switches without a feedback signal, interconnect the corresponding control bit as the signal source:
BI: p1269[0] = r1261.0
BI: p1269[1] = r1261.1
p1267 Bypass changeover source configuration / Chngov_src config
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Bypass via signal (BI: p1266) Yes No -
01 Bypass via reaching the speed threshold Yes No -
p1268 BI: Bypass feedback synchronization completed / FS sync compl
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
- - 3819.2
p1269[0...1] BI: Bypass switch feedback signal / Bypass FS
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
- - 0