2 Parameters
2.2 List of parameters
SINAMICS G130/G150
778 List Manual (LH2), 07/2016, A5E03263479A
4: Phase current W
5: IGBT chip temperature
6: Heat sink temperature
7: DC link voltage
8: Modulat_depth
9: Angle
Index: [0] = Trace channel 0
[1] = Trace channel 1
[2] = Trace channel 2
[3] = Trace channel 3
[4] = Trace channel 4
[5] = Trace channel 5
[6] = Trace channel 6
[7] = Trace channel 7
[8] = Trace channel 8
[9] = Trace channel 9
[10] = Trace channel 10
[11] = Trace channel 11
[12] = Trace channel 12
[13] = Trace channel 13
[14] = Trace channel 14
[15] = Trace channel 15
Dependency: Refer to: p7791, p7792
Refer to: A01302
Note: In the operation state, when a trigger event occurs, the trace data of the signals are saved in the component. The
oldest trace data are overwritten after more than 5 trigger events.
The trigger event can be set in p7791.
By activating p7792, the trace data of the component is written to files on the non-volatile storage medium (memory
card). Experts can then evaluate this data.
Description: Sets the trigger event for the component trace.
Value: 0: Overcurrent, overvoltage, ground fault, Uce
1: Time-critical message
2: Uce
Dependency: Refer to: p7790, p7792
Note: F30001 is output if the power unit detects an overcurrent condition.
F30002 is output if the power unit detects an overvoltage condition in the DC link.
F30021 is output if the power unit detects a ground fault.
F30022 is output if the power unit detects an Uce fault.
Description: Setting to upload and save the trace data of the component trace.
Experts can then evaluate this data.
For p7792 = 1, the trace data of the component is written to files on the memory card in a non-volatile fashion.
The parameter is then automatically set to zero.
p7791 Component trace trigger / Comp trace trigger
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 0
p7792 Upload component trace data / Upload comp trace
VECTOR_G, B_INF Can be changed: U, T Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0