Siemens G130 - r0077 CO: Current setpoint torque-generating; Iq_set; r0078 CO: Current actual value torque-generating; Iq_act; r0079 CO: Torque setpoint; M_set; r0080[0...1] CO: Torque actual value; M_act

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
68 List Manual (LH2), 07/2016, A5E03263479A
Description: Display and connector output for the torque/force-generating current setpoint.
Note: This value is irrelevant for the U/f control mode.
Description: Display and connector output for the torque-generating current actual value (Iq_act).
Dependency: Refer to: r0030
Note: This value is irrelevant for the U/f control mode.
The torque-generating current actual value is available smoothed (r0030 with 300 ms) and unsmoothed (r0078).
Description: Display and connector output for the torque setpoint at the output of the speed controller.
Description: Display and connector output for actual torque value.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0031, p0045
Note: The value is available smoothed (r0031 with 100 ms, r0080[1] with p0045) and unsmoothed (r0080[0]).
r0077 CO: Current setpoint torque-generating / Iq_set
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6700, 6710
P-Group: Displays, signals Unit group: 6_2 Unit selection: p0505
Not for motor type: REL Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0078 CO: Current actual value torque-generating / Iq_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6310, 6700,
6714, 6799
P-Group: Displays, signals Unit group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0079 CO: Torque setpoint / M_set
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6020, 6060,
6710
P-Group: Displays, signals Unit group: 7_1 Unit selection: p0505
Not for motor type: REL Scaling: p2003 Expert list: 1
Min Max Factory setting
- [Nm] - [Nm] - [Nm]
r0080[0...1] CO: Torque actual value / M_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6714, 6799
P-Group: Displays, signals Unit group: 7_1 Unit selection: p0505
Not for motor type: - Scaling: p2003 Expert list: 1
Min Max Factory setting
- [Nm] - [Nm] - [Nm]