Siemens G130 - p2247[0...n] Technology controller motorized potentiometer ramp-up time; Tec_ctr mop t_r­up; p2248[0...n] Technology controller motorized potentiometer ramp-down time; Tec_ctrMop t_rdown; r2250 CO: Technology controller motorized potentiometer setpoint after RFG; Tec_ctr mop aftRFG; p2252 Technology controller configuration; Tec_ctrl config

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
570 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2248
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
Description: Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency: Refer to: p2247
Note: The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
Description: Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency: Refer to: r2245
Description: Sets the configuration of the technology controller.
p2247[0...n] Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]
p2248[0...n] Technology controller motorized potentiometer ramp-down time /
Tec_ctrMop t_rdown
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7954
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 1000.0 [s] 10.0 [s]
r2250 CO: Technology controller motorized potentiometer setpoint after RFG /
Tec_ctr mop aftRFG
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7954
P-Group: Technology Unit group: 9_1 Unit selection: p0595
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p2252 Technology controller configuration / Tec_ctrl config
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ramp-up/down time independent of
setpoint sign
Yes No -
01 Integrator independent of Kp Yes No -
02 Output signal without ramp active Yes No -
03 Act value limit Yes No -