Siemens G130 - A01224 CU: Pulse frequency inconsistent; F01250 CU: CU-EEPROM incorrect read-only data; A01251 CU: CU-EEPROM incorrect read-write data

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1396 List Manual (LH2), 07/2016, A5E03263479A
General note:
The topology rules should be noted when connecting up DRIVE-CLiQ (refer to the appropriate product
documentation).
The parameters of the sampling times can also be changed with automatic calculations.
Example for highest common denominator: 125 s, 125 µs, 62.5 µs --> 62.5 µs
Remedy: - check the DRIVE-CLiQ cables.
- set a valid sampling time.
See also: p0115, p0799, p4099
A01224 CU: Pulse frequency inconsistent
Message value: %1
Message class: Error in the parameterization / configuration / commissioning procedure (18)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: When changing the minimum pulse frequency (p0113) inconsistency between the pulse frequencies was identified.
Alarm value (r2124, interpret decimal):
1: Value lower than minimum value.
2: Value higher than maximum value.
3: Resulting sampling time is not a multiple of 1.25 µs.
4: Value does not match clock-cycle synchronous PROFIBUS operation.
10: Special restriction of the drive object violated.
99: Inconsistency of cross drive objects detected.
116: Recommended clock cycle in r0116[0...1].
Remedy: Set a valid pulse frequency.
See also: p0113 (Minimum pulse frequency, selection)
F01250 CU: CU-EEPROM incorrect read-only data
Message value: %1
Message class: Hardware/software error (1)
Drive object: All objects
Component: Control Unit (CU) Propagation: LOCAL
Reaction: NONE (OFF2)
Acknowledge: POWER ON
Cause: Error when reading the read-only data of the EEPROM in the Control Unit.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON.
- replace the Control Unit.
A01251 CU: CU-EEPROM incorrect read-write data
Message value: %1
Message class: Hardware/software error (1)
Drive object: All objects
Component: Control Unit (CU) Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: Error when reading the read-write data of the EEPROM in the Control Unit.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: For alarm value r2124 < 256, the following applies:
- carry out a POWER ON.
- replace the Control Unit.