SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
233
2 Parameters
2.2 List of parameters
Description: Sets the signal source to evaluate the motor temperature via a BICO interconnection.
Dependency: Refer to: p0600
Note: Temperature sensor KTY/PT1000: Valid temperature range -48 °C ... 248 °C.
PTC temperature sensor:
For a value = -50 °C, the following applies: Motor temperature < nominal response temperature of the PTC.
For a value = 250 °C, the following applies: Motor temperature >= nominal response temperature of the PTC.
Note:
When using a Terminal Module 31 (TM31), the following applies:
- the sensor type used is set using p4100.
- the temperature signal is interconnected using CO: r4105.
Description: Sets the alarm threshold for monitoring the motor temperature for motor temperature model 2 or KTY/PT1000.
After the alarm threshold is exceeded, alarm A07910 is output and timer (p0606) is started.
If the delay time has expired and the alarm threshold has, in the meantime, not been fallen below, then fault F07011
is output.
Dependency: Refer to: p0606, p0612
Refer to: F07011, A07910
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Sets the threshold and temperature value to monitor the motor temperature.
Temperature model 1 (I2t, p0612.0 = 1):
The following applies for firmware version < 4.7 SP6 or p0612.8 = 0:
- sets the alarm threshold. If the model temperature (r0034) exceeds the alarm threshold, then alarm A07012 is
output.
- this value is simultaneously used as rated winding temperature.
p0603 CI: Motor temperature signal source / Mot temp S_src
VECTOR_G Can be changed: C2(3), T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 8016
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
- - 0
p0604[0...n] Mot_temp_mod 2: sensor alarm threshold / Mod 2: sens A_thr
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Unit group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 130.0 [°C]
p0605[0...n] Mot_temp_mod 1/2 sensor threshold and temperature value / Mod 1/2 sens thr_T
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8016, 8017
P-Group: Motor Unit group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 240.0 [°C] 145.0 [°C]