2 Parameters
2.2 List of parameters
SINAMICS G130/G150
876 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the station name for the Industrial Ethernet interface (X127) on the Control Unit.
The actual station name is displayed in r8910.
Dependency: Refer to: p8905, r8910
Note: An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
The interface configuration (p8900 and following) is activated with p8905 = 1.
The parameter is not influenced by setting the factory setting.
IE: Industrial Ethernet
Description: Sets the IP address for the Industrial Ethernet interface (X127) on the Control Unit.
The actual IP address is displayed in r8911.
Dependency: Refer to: p8905, r8911
Note: The interface configuration (p8900 and following) is activated with p8905 = 1.
The parameter is not influenced by setting the factory setting.
Description: Sets the default gateway for the Industrial Ethernet interface (X127) on the Control Unit.
The actual default gateway is displayed in r8912.
Dependency: Refer to: p8905, r8912
Note: The setting p8902[0...3] = 0 or p8902 = p8901 (own IP address) means that a standard gateway has not been set.
The interface configuration (p8900 and following) is activated with p8905 = 1.
The parameter is not influenced by setting the factory setting.
Description: Sets the subnet mask for the Industrial Ethernet interface (X127) on the Control Unit.
The actual subnet mask is displayed in r8913.
Dependency: Refer to: p8905, r8913
p8900[0...239] IE Name of Station / IE Name Stat
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p8901[0...3] IE IP address / IE IP addr
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8902[0...3] IE def gateway / IE Def Gateway
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p8903[0...3] IE Subnet Mask / IE Subnet Mask
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0