SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
511
2 Parameters
2.2 List of parameters
Description: Status display for the PROFIBUS interface.
Value: 0: OFF
1: No connection (search for baud rate)
2: Connection OK (baud rate found)
3: Cyclic connection with master (data exchange)
4: Cyclic data OK
Note: For r2054 = 3:
In state 3 (the LED flashes green), a cyclic connection has been established to the PROFIBUS master; however, one
of the following prerequisites is missing for cyclic operation:
- no setpoints are being received as the PROFIBUS master is in the STOP condition.
Only for clock-cycle synchronous operation, the following applies:
- the drive is not in synchronism as the global control (GC) has an error.
For r2054 = 4:
In the status 4 (LED green), the cyclic connection to the PROFIBUS master has been established and setpoints are
being received. The clock cycle synchronization is OK, the global control (GC) is error-free.
This state does not provide any statement regarding the quality of the clock cycle synchronous sign-of-life characters
on the drive objects.
Description: Diagnostics display for the PROFIBUS interface.
Index: [0] = Master bus address
[1] = Master input total length bytes
[2] = Master output total length bytes
Description: Displays the setting of the PROFIBUS address switch "DP ADDRESS" on the Control Unit.
Dependency: Refer to: p0918
Notice: The display is updated after switching on, and not cyclically.
r2054 PROFIBUS status / PB status
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 2410
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 4 -
r2055[0...2] PROFIBUS diagnostics standard / PB diag standard
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2410
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r2057 PROFIBUS address switch diagnostics / PB addr sw diag
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2410
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -