EasyManua.ls Logo

Siemens G130 - F01255 CU: Option Board EEPROM read-only data error; A01256 CU: Option Board EEPROM read-write data error; A01302 Error in the component trace

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1397
4 Faults and alarms
4.2 List of faults and alarms
For alarm value r2124 >= 256, the following applies:
- for the drive object with this alarm, clear the fault memory (p0952 = 0).
- as an alternative, clear the fault memory of all drive objects (p2147 = 1).
- replace the Control Unit.
F01255 CU: Option Board EEPROM read-only data error
Message value: %1
Message class: Hardware/software error (1)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE (OFF2)
Acknowledge: POWER ON
Cause: Error when reading the read-only data of the EEPROM in the Option Board.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON.
- replace the Control Unit.
A01256 CU: Option Board EEPROM read-write data error
Message value: %1
Message class: Hardware/software error (1)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: Error when reading the read-write data of the EEPROM in the Option Board.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - carry out a POWER ON (switch-off/switch-on).
- replace the Control Unit.
A01302 Error in the component trace
Message value: %1
Message class: General drive fault (19)
Drive object: B_INF, VECTOR_G
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: An error has occurred in the component trace.
The message appears in the following cases:
- upload trace data (p7792 = 1).
- change factory setting (p7790, p7791) for missing property "component trace" (r0193.1 = 0).
Alarm value (r2124, interpret decimal):
1: The DRIVE-CLiQ component does not support the component trace (r0193.1 = 0).
101: Data from trace 1 cannot be read.
102: Data from trace 2 cannot be read.
103: Data from trace 3 cannot be read.
104: Data from trace 4 cannot be read.
105: Data from trace 5 cannot be read.
Remedy: For alarm value = 1:
Upgrade the firmware of the DRIVE-CLiQ component involved.

Table of Contents