2 Parameters
2.2 List of parameters
SINAMICS G130/G150
620 List Manual (LH2), 07/2016, A5E03263479A
Note: Synchronism is reached (r3819.2 = 1), if the AND logic operation of the results from the phase measurement (p3813)
and voltage measurement (p3815) is fulfilled.
For voltage manipulated quantity margin (reserve) of the drive converter, the amplitude difference (r3814) between
the setpoint and actual value is controlled (corrected) to zero.
Description: Displays the status word for the line-drive synchronization.
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 1st value pair of the friction characteristic.
Dependency: Refer to: p3830, p3845
Description: The friction characteristic is defined by 10 value pairs.
This parameter specifies the n coordinate of the 2nd value pair of the friction characteristic.
Dependency: Refer to: p3831, p3845
r3819.0...7 CO/BO: Sync-line-drive status word / Sync ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Sync-line-drive enabled Yes No -
02 Sync-line-drive synchronism reached Yes No -
03 Sync-line-drive synchronizing error Yes No -
05 Sync-line-drive frequency measurement
active
Yes No -
06 Sync-line-drive phase control active Yes No -
07 Sync-line-drive without drive Yes No -
p3820[0...n] Friction characteristic value n0 / Friction n0
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Unit group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 15.00 [rpm]
p3821[0...n] Friction characteristic value n1 / Friction n1
VECTOR_G (n/M) Can be changed: T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7010
P-Group: Functions Unit group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 30.00 [rpm]