2 Parameters
2.2 List of parameters
SINAMICS G130/G150
290 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the send and receive telegram.
Value: 390: SIEMENS telegram 390, PZD-2/2
391: SIEMENS telegram 391, PZD-3/7
392: SIEMENS telegram 392, PZD-3/15
393: SIEMENS telegram 393, PZD-4/21
394: SIEMENS telegram 394, PZD-3/3
395: SIEMENS telegram 395, PZD-4/25
999: Free telegram configuration with BICO
Description: Sets the send and receive telegram.
Value: 1: Standard telegram 1, PZD-2/2
2: Standard telegram 2, PZD-4/4
20: Standard telegram 20, PZD-2/6
220: SIEMENS telegram 220, PZD-10/10
352: SIEMENS telegram 352, PZD-6/6
999: Free telegram configuration with BICO
Caution: Telegrams 2, 3 and 4 are not suitable for sensorless vector control (p1300 = 20). For sensorless vector control, it is
necessary that the setpoint speed is entered at the ramp-function generator input (e.g. p1070) and not after the
ramp-function generator (p1155).
Note: If a value is not equal to 999, a telegram is set and the automatically set interconnections in the telegram are
inhibited. The inhibited interconnections can only be changed again after setting value 999.
Description: Sets the send and receive telegram.
Value: 1: Standard telegram 1, PZD-2/2
2: Standard telegram 2, PZD-4/4
3: Standard telegram 3, PZD-5/9
4: Standard telegram 4, PZD-6/14
20: Standard telegram 20, PZD-2/6
220: SIEMENS telegram 220, PZD-10/10
352: SIEMENS telegram 352, PZD-6/6
999: Free telegram configuration with BICO
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 2401, 2420,
2423, 2481, 2483
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
390 999 999
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
VECTOR_G Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 2401, 2415,
2416, 2419, 2420, 2421, 2422,
2423
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 999 999
p0922 IF1 PROFIdrive PZD telegram selection / IF1 PZD telegr
VECTOR_G (n/M) Can be changed: C2(1), T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 2401, 2415,
2416, 2419, 2420, 2421, 2422,
2423
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 999 999