2 Parameters
2.2 List of parameters
SINAMICS G130/G150
116 List Manual (LH2), 07/2016, A5E03263479A
For bit 03 = 1:
The DC link voltage limit is set to the maximum value of the power unit.
For bit 05 = 1:
The status of the inputs/outputs for the power unit contactors is displayed in r0256.
This only applies to chassis power units with 3 AC line connection and line contactors.
The status display is only effective after parameter save and POWER ON.
Description: Sets the power unit configuration.
Dependency: For bit 00:
Reduced supply voltages are only possible for booksize and chassis power units (DC/AC).
Bit 0 = 1 can only be set if r0192.22 = 1.
For bit 01 = 1:
The external precharging setting only affects the DC/AC power units.
For bit 03 = 1:
The automatic adaptation (reduction) of the Vdc max limit is deactivated (only for chassis power units). Bit 3 only has
an effect, if bit 0 is simultaneously set.
Refer to: r0192, p0210
Caution: For bit 00:
Working with reduced input voltages deactivates undervoltage detection.
For bit 03:
If the automatic setting of the Vdc max limit is deactivated, then all of the components connected to the DC link must
be suitable for the maximum DC link voltage of the power unit (e.g. 820 V for 400 V units).
Note: For bit 00 = 0:
It is not possible to reduce the supply voltage in p0210.
For bit 00 = 1:
With this setting the supply voltage in p0210 can be reduced to 100 V.
Booksize PU: only for operating mode p1300 = 19
Chassis PU: only for operating mode p1300 > 19 and closed-loop DC voltage control
For bit 01 = 0:
There is no external precharging of the DC/AC Motor Modules. The precharging monitoring is bypassed.
For bit 01 = 1:
There is external precharging of the DC/AC Motor Modules. The precharging monitoring is calculated.
For bit 03 = 0:
The DC link voltage limit is calculated from p0210.
For bit 03 = 1:
The DC link voltage limit is set to the maximum value of the power unit.
For bit 05 = 1:
The status of the inputs/outputs for the power unit contactors is displayed in r0256.
This only applies to chassis power units with 3 AC line connection and line contactors.
The status display is only effective after parameter save and POWER ON.
p0212 Power unit configuration / PU config
VECTOR_G (n/M) Can be changed: C2(2) Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Drive unit line supply voltage reduced Yes No -
01 External precharging present Yes No -
03 Automatically adapt Vdc_max limit No Yes -
05 Contactor display inputs/outputs status Yes No 9814
06 Reduction of the permissible minimum
voltage during precharging
Yes No -