SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
39
2 Parameters
2.2 List of parameters
Notice: The display filter via p0004 provides precise filtering and displays the corresponding parameters only when p0009
and p0010 = 0.
Note: The set access level via p0003 is also relevant for the display filter via p0004.
Examples (assumption: p0009 = p0010 = 0):
p0003 = 1, p0004 = 3
--> Only the parameters for the motor with access level 1 are displayed.
p0003 = 2, p0004 = 3
--> Only the parameters for the motor with access levels 1 and 2 are displayed.
Description: Sets the parameter number and parameter index for display for p0006 = 2, 4 for the Basic Operator Panel (BOP).
Examples for the SERVO drive object:
p0005[0] = 21, p0005[1] = 0: Actual speed smoothed (r0021)
p0005[0] = 25, p0005[1] = 0: Output voltage smoothed (r0025)
Index: [0] = Parameter number
[1] = Parameter index
Dependency: Refer to: p0006
Note: Procedure:
1.
The parameter number to be displayed should be set in index 0. Only the monitoring parameters (read-only
parameters) can be set that actually exist for the actual drive object.
If the set parameter number is not indexed, or if there is an index in index 1 that lies outside the valid range of the set
parameter, then index 1 is automatically set to 0.
2.
The index that belongs to the parameter set in index 0 should be set in index 1. The permissible changes in index 1
always depend on the parameter number set in index 0.
Description: Sets the mode of the operating display for the Basic Operator Panel (BOP) in the operating states "ready for
operation" and "operation".
Value: 4: p0005
Dependency: Refer to: p0005
Note: Mode 0 ... 3 can only be selected if also r0020, r0021 are available on the drive object.
Mode 4 is available for all drive objects.
p0005[0...1] BOP operating display selection / BOP op_disp sel
All objects Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 [0] 2
[1] 0
p0006 BOP operating display mode / BOP op_ disp mode
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP, TM31,
TM120, TM150, TB30,
TM54F_MA,
TM54F_SL, ENC, HUB
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
4 4 4