SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
679
2 Parameters
2.2 List of parameters
Description: Display and connector output for the average value of each group for the Terminal Module 150 (TM150).
This value is calculated from the actual temperature values (r4105[0...11]) of each group.
Recommendation: The following connector inputs can use these connector outputs for interconnection:
- CI: p0603
- CI: p0608[0...3]
- CI: p0609[0...3]
- CI: p2051
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4112, r4113
Note: If one group is assigned sensor type "PTC" or "bimetal NC contact", then the average value -300 °C is output.
Description: Sets the effect for an error of a sensor of a group for Terminal Module TM150 (TM150).
For p4117 = 0, the following applies:
The defective temperature sensor assigned to a group is not take into account when forming the group.
For p4117 = 1, the following applies:
For a sensor error, for the maximum value, minimum value and average value of the corresponding group, a value of
-300 °C is output.
Value: 0: Skip sensor
1: Output value = -300 °C
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4112, r4113, r4114
Description: Sets the hysteresis for the fault threshold/alarm threshold (p4102[0...23]) for the Terminal Module 150 (TM150).
Index: [0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
r4114[0...2] CO: TM150 group temperature average actual value / TM150 grp temp av
TM150 Can be changed: - Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9625
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: p2006 Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
p4117[0...2] TM150 group sensor error effect / TM150 error effect
TM150 Can be changed: U, T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9625
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4118[0...11] TM150 fault threshold/alarm threshold hysteresis / TM150 thresh hyst
TM150 Can be changed: T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [K] 50 [K] 5 [K]