EasyManua.ls Logo

Siemens G130 - p0453[0...n] Pulse encoder evaluation zero speed measuring time; Enc_ev n_0 t_meas; r0455[0...2] Encoder configuration recognized; Enc_config recog

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
184 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the measuring time for evaluating zero speed.
If no pulses are detected from track A/B during this time, a speed actual value of zero is output.
Dependency: Refer to: r0452
Note: This function is required for slow-running motors so that actual speeds close to zero can be output correctly.
Description: Displays the detected encoder configuration.
In this case, the encoder must automatically support the function (e.g. encoder with EnDat interface).
Index: [0] = Encoder 1
[1] = Encoder 2
[2] = Encoder 3
Dependency: Refer to: p0404
Note: ZM: Zero mark
This parameter is only used for diagnostics.
A value of zero is displayed if an encoder is not present.
For bit 20, 21 (voltage level 5 V, voltage level 24 V):
The voltage level cannot be detected. Therefore, these bits are always set to 0.
p0453[0...n] Pulse encoder evaluation zero speed measuring time / Enc_ev n_0 t_meas
VECTOR_G, ENC Can be changed: C2(4) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.10 [ms] 10000.00 [ms] 1000.00 [ms]
r0455[0...2] Encoder configuration recognized / Enc_config recog
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Linear encoder Yes No -
01 Absolute encoder Yes No -
02 Multiturn encoder Yes No -
03 Track A/B sq-wave Yes No -
04 Track A/B sine Yes No -
05 Track C/D Yes No -
06 Hall sensor Yes No -
08 EnDat encoder Yes No -
09 SSI encoder Yes No -
10 DRIVE-CLiQ encoder Yes No -
11 Digital encoder Yes No -
12 Equidistant zero mark Yes No -
13 Irregular zero mark Yes No -
14 Distance-coded zero mark Yes No -
15 Commutation with zero mark (not ASM) Yes No -
16 Acceleration Yes No -
17 Track A/B analog Yes No -
20 Voltage level 5 V Yes No -
21 Voltage level 24 V Yes No -
22 Remote sense (only SMC30) Yes No -
23 Resolver excit Yes No -

Table of Contents