SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
613
2 Parameters
2.2 List of parameters
Description: Sets CT gain of the CT connected at the 10 V input of the Voltage Sensing Module (VSM).
The parameter specifies the current magnitude in [A] referred to the input voltage at the VSM in [V].
Example:
CT with 1 V per 200 A.
--> p3670 = 200
Dependency: Refer to: r3671, r3672
Note: The CT for phase 1 is connected at terminals X520.1 and X520.2 of the VSM.
The CT for phase 2 is connected at terminals X520.3 and X520.4 of the VSM.
Description: Displays the current actual value from current transducer (CT) 1 at the 10 V input of the Voltage Sensing Module
(VSM).
Dependency: Refer to: p3670
Note: The CT for phase 1 is connected at terminals X520.1 and X520.2 of the VSM.
Description: Displays the current actual value from current transducer (CT) 2 at the 10 V input of the Voltage Sensing Module
(VSM).
Dependency: Refer to: p3670
Note: The CT for phase 2 is connected at terminals X520.3 and X520.4 of the VSM.
Description: Displays the actual value of the voltage measured at the 10 V input 1 of the Voltage Sensing Module (VSM).
Dependency: Refer to: p3670
Note: 10 V input 1: Terminals X520.1 and X520.2
p3670[0...n] VSM 10 V input CT gain / VSM CT_gain
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
0.000 [A] 1000.000 [A] 1.000 [A]
r3671[0...n] CO: VSM 10 V input CT 1 actual value / VSM CT 1 I_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r3672[0...n] CO: VSM 10 V input CT 2 actual value / VSM CT 2 I_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r3673[0...n] CO: VSM 10 V input 1 actual value / VSM inp 1 U_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: p0150 Func. diagram: 9880
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]