2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1036 List Manual (LH2), 07/2016, A5E03263479A
Description: Select a fail-safe digital input (F-DI) for the signal "acknowledge internal event" (internal fault).
The signal is transferred to the corresponding control signal of all drives.
The falling edge at this input resets the status "internal event" in the drives.
The rising edge at this input acknowledges any existing discrepancy errors.
Value: 0: Static selected
1: F-DI 0 (X521.2/3/6)
2: F-DI 1 (X521.4/5/7)
3: F-DI 2 (X522.1/2/7)
4: F-DI 3 (X522.3/4/8)
5: F-DI 4 (X522.5/6/9)
6: F-DI 5 (X531.2/3/6)
7: F-DI 6 (X531.4/5/7)
8: F-DI 7 (X532.1/2/7)
9: F-DI 8 (X532.3/4/8)
10: F-DI 9 (X532.5/6/9)
255: Static deselected
Dependency: Refer to: A35081
Note: The values "static selected" and "static deselected" result in an inactive function of the safe acknowledgment.
F-DI: Failsafe Digital Input
Description: Sets the signal source to initiate the test stop.
For example, a digital input of the Control Unit or one of the other Terminal Modules can be set as signal source.
The test stop is triggered on a 0/1 signal edge.
The TM54F must be in the "ready" state (p0010 = 0).
Dependency: Refer to: p10001, p10003, p10041, p10046
Notice: Digital inputs of the TM54F must not be used to trigger the test stop.
Description: Sets the operating mode for the Terminal Module 54F (TM54F).
Value: 0: Function interface
1: Control interface
Note: Parameter being prepared. For this firmware version, the function interface is not supported.
p10006 SI TM54F acknowledgment internal event input terminal / SI ackn int event
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 2900, 2905
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p10007 BI: SI TM54F forced checking procedure F-DI/F-DO signal source / SI dynF-DI/DOs_src
TM54F_MA Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2892
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p10008 SI TM54F operating mode / SI op_mod
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 1