2 Parameters
2.2 List of parameters
SINAMICS G130/G150
768 List Manual (LH2), 07/2016, A5E03263479A
Note: The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 2:
1. Switch off the system and replace valve 2.
2. Switch on the system and acknowledge that valve 2 has been replaced (p7786.2 = 1).
--> the power cycling counter of valve 2 is reset (r7741 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.2 is automatically set to 0.
Description: Displays the status of power cycling counter for valve 3.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
Dependency: Refer to: p7786
Notice: After a valve has been replaced, the corresponding power cycling counter must be reset.
Note: The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 3:
1. Switch off the system and replace valve 3.
2. Switch on the system and acknowledge that valve 3 has been replaced (p7786.3 = 1).
--> the power cycling counter of valve 3 is reset (r7742 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.3 is automatically set to 0.
Description: Displays the status of power cycling counter for valve 4.
For repairs, this parameter serves as internal documentation for service personnel.
The counter state corresponds to the valve wear. A maximum of 650% of the specified service life is displayed.
Dependency: Refer to: p7786
Notice: After a valve has been replaced, the corresponding power cycling counter must be reset.
Note: The IGBT power cycling counter can only be set to 0.
Procedure when replacing valve 4:
1. Switch off the system and replace valve 4.
2. Switch on the system and acknowledge that valve 4 has been replaced (p7786.4 = 1).
--> the power cycling counter of valve 4 is reset (r7743 = 0).
3. Carry out a POWER ON (switch-off/switch-on).
--> as a consequence p7786.4 is automatically set to 0.
r7742[0...n] IGBT power cycling counter valve 3 / IGBT load count 3
VECTOR_G, B_INF Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r7743[0...n] IGBT power cycling counter valve 4 / IGBT load count 4
VECTOR_G, B_INF Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: PDS, p0120 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -