Siemens G130 - p10040 SI TM54 F F-DI input mode; SI F­DI inp_mode; p10041 SI TM54 F F-DI enable for test; SI F­DI enab test

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
1049
2 Parameters
2.2 List of parameters
Description: Sets the input mode for the safety digital inputs (F-DI).
Note: Only an NC contact can be connected for the safety digital inputs not listed.
Description: Enable signal for the integration of F-DI in the test (forced checking procedure) of the sensor power supply.
Note: F-DI: Failsafe Digital Input
Bit field: Bit Signal name 1 signal 0 signal FP
00 Power_removed Selected Not selected -
01 SS1_active Selected Not selected -
02 SS2_active Selected Not selected -
03 SOS_active Selected Not selected -
04 SLS_active Selected Not selected -
05 SDI_pos_active Selected Not selected -
06 SDI_neg_active Selected Not selected -
07 SLP_active Selected Not selected -
p10040 SI TM54F F-DI input mode / SI F-DI inp_mode
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 0, DI 1+ (X521.3) NO contact NC contact 2893
01 F-DI 1, DI 3+ (X521.5) NO contact NC contact 2893
02 F-DI 2, DI 5+ (X522.2) NO contact NC contact 2893
03 F-DI 3, DI 7+ (X522.4) NO contact NC contact 2893
04 F-DI 4, DI 9+ (X522.6) NO contact NC contact 2893
05 F-DI 5, DI 11+ (X531.3) NO contact NC contact 2894
06 F-DI 6, DI 13+ (X531.5) NO contact NC contact 2894
07 F-DI 7, DI 15+ (X532.2) NO contact NC contact 2894
08 F-DI 8, DI 17+ (X532.4) NO contact NC contact 2894
09 F-DI 9, DI 19+ (X532.6) NO contact NC contact 2894
p10041 SI TM54F F-DI enable for test / SI F-DI enab test
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 2892
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 0, power supply L1+ Test active No test -
01 F-DI 1, power supply L1+ Test active No test -
02 F-DI 2, power supply L1+ Test active No test -
03 F-DI 3, power supply L1+ Test active No test -
04 F-DI 4, power supply L1+ Test active No test -
05 F-DI 5, power supply L2+ Test active No test -
06 F-DI 6, power supply L2+ Test active No test -
07 F-DI 7, power supply L2+ Test active No test -
08 F-DI 8, power supply L2+ Test active No test -
09 F-DI 9, power supply L2+ Test active No test -