2 Parameters
2.2 List of parameters
SINAMICS G130/G150
576 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the proportional gain (P component) of the technology controller.
Dependency: Refer to: p2252
Note: p2280 = 0: The proportional gain is disabled.
Description: Sets the integral time (I component, integrating time constant) of the technology controller.
Dependency: Refer to: p2252
Note: p2285 = 0: The integral time is disabled.
Description: Sets the signal source to hold the integrator for the technology controller.
Description: Sets the signal source for the pre-control signal of the technology controller.
Description: Sets the maximum limit of the technology controller.
Dependency: Refer to: p2292
Caution: The maximum limit must always be greater than the minimum limit (p2291 > p2292).
p2280 Technology controller proportional gain / Tec_ctrl Kp
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 1000.000 1.000
p2285 Technology controller integral time / Tec_ctrl Tn
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 60.000 [s] 0.000 [s]
p2286[0...n] BI: Hold technology controller integrator / Tec_ctr integ hold
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p2289[0...n] CI: Technology controller pre-control signal / Tec_ctr prectr_sig
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 0
p2291 CO: Technology controller maximum limiting / Tec_ctrl max_lim
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7958
P-Group: Technology Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-200.00 [%] 200.00 [%] 100.00 [%]