2 Parameters
2.2 List of parameters
SINAMICS G130/G150
318 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the signal source for scaling the main setpoint.
Description: Displays the effective main setpoint.
The value shown is the main setpoint after scaling.
Description: Sets the signal source for the supplementary setpoint.
Dependency: Refer to: p1076, r1077, r1078
Description: Sets the signal source for scaling the supplementary setpoint.
Description: Displays the effective supplementary setpoint. The value shown is the additional setpoint after scaling.
p1071[0...n] CI: Main setpoint scaling / Main setp scal
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3030
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 1
r1073 CO: Main setpoint effective / Main setpoint eff
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3030
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1075[0...n] CI: Suppl setp / Suppl setp
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3030
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0
p1076[0...n] CI: Supplementary setpoint scaling / Suppl setp scal
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3030
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 1
r1077 CO: Supplementary setpoint effective / Suppl setpoint eff
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3030
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]