2 Parameters
2.2 List of parameters
SINAMICS G130/G150
694 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the output voltage range to be mapped for the connected analog sensor.
The voltage range is determined by the following parameters:
- p4674 (voltage at actual value 0)
- p4675 (voltage per encoder period)
Note: The minimum actual value which can be mapped is equal to p4674 - p4675/2.
The maximum actual value which can be mapped is equal to p4674 + p4675/2.
Description: Sets the threshold for limit monitoring of the absolute actual value on the analog sensor.
If this threshold is overshot by the actual value of a channel, a corresponding fault/alarm (p4670.9) is output.
Dependency: Refer to: p4673, p4675
Description: Sets the configuration for LVDT mode on the analog sensor.
Description: Sets the ratio for the LVDT sensor.
p4675[0...n] Analog sensor channel B voltage per encoder period / Ana_sens B U/per
VECTOR_G, ENC Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-10.0000 [V] 10.0000 [V] 6.0000 [V]
p4676[0...n] Analog sensor range limit threshold / Ana_sens lim thr
VECTOR_G, ENC Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] 100.0 [%]
p4677[0...n] Analog sensor LVDT configuration / Ana_sens LVDT conf
VECTOR_G, ENC Can be changed: C2(4) Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 LVDT ON Yes No -
01 Track B excitation Yes No -
02 Fixed value amplitude Yes No -
03 Fixed value amplitude and phase Yes No -
p4678[0...n] Analog sensor LVDT ratio / An_sens LVDT ratio
VECTOR_G, ENC Can be changed: C2(4) Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: EDS, p0140 Func. diagram: -
P-Group: Encoder Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 200.00 [%] 50.00 [%]