SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
155
2 Parameters
2.2 List of parameters
Description: Displays the damping resistance of the separately excited synchronous motor quadrature to the rotor direction (q
axis).
Description: Displays the nominal rotor / secondary section resistance of the motor at the rated temperature.
The rated temperature is the sum of p0625 and p0628.
Dependency: Refer to: p0628
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Displays the total stray inductance of the motor.
Induction motor, separately excited synchronous motor:
Displays the stator leakage inductance of the motor, including the series inductance (p0353) and the motor reactor
(p0233).
Synchronous motor:
Displays the stator quadrature inductance, including the series inductance (p0353) and the motor reactor (p0233).
Description: Displays the stator longitudinal inductance of the synchronous motor including the series inductance (p0353) and the
motor reactor (p0233).
Note: The parameter is not used for separately excited synchronous motors (p0300 = 5).
r0375[0...n] Motor damping resistance q axis / Mot R_damp q
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: ASM, PMSM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0376[0...n] Rated motor rotor resistance / Mot rated R_rotor
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 16_1 Unit selection: p0349
Not for motor type: PMSM, SESM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
- [ohm] - [ohm] - [ohm]
r0377[0...n] Motor leakage inductance total / Mot L_leak total
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6640
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [mH] - [mH] - [mH]
r0378[0...n] Motor stator inductance d axis / Mot L_stator d
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: 15_1 Unit selection: p0349
Not for motor type: ASM, SESM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [mH] - [mH] - [mH]