2 Parameters
2.2 List of parameters
SINAMICS G130/G150
470 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the configuration of the actual value correction.
Dependency: Refer to: p1802
Note: During operation (pulses enabled) the configuration cannot be changed by changing over drive data sets.
Description: Displays the status of actual value correction.
11 Short-circuit test active No Yes -
12 FL modulation prohibited Yes No -
13 F3E present Yes No -
14 Angle prerotation (advance) active in SW Yes No -
15 Power unit with PS interface Yes No -
16 Current measurement oversampling active Yes No -
17 Actual value averaging temporarily
suppressed
Yes No -
18 Modulation depth limiting Yes No -
19 Reduced DC link capacitance (without F3E) Yes No -
20 The setpoint is not reset Yes No -
21 Voltage calibration active Yes No -
22 Vdc correction deactivated in the gating unit Yes No -
p1840[0...n] Actual value correction configuration / ActVal_corr conf
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Actual value correction deactivated Yes No -
01 Compares the integrals from modulator and
setpoint
Yes No -
r1841 Actual value correction status word / ActVal_corr status
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Hardware for the actual value correction
detected
Yes No -
01 Automatic shutdown (too many switching
instants)
Yes No -
02 Integral scaled to half the gating unit clock
cycle freq.
Yes No -
03 Actual value correction temporarily
suppressed
Yes No -
14 Reserved Yes No -
15 Actual value correction active Yes No -