2 Parameters
2.2 List of parameters
Description: Sets the dead time for non-synchronized bypass.
Note: This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-
magnetizing time of the motor (p0347).
The total changeover time for the bypass is based on the total of p1262 plus the OFF time for the relevant switch
(p1274[x]).
Description: Sets the delay time to switch back to converter operation for a non-synchronized bypass.
Description: Sets the delay time for switching to line operation for a non-synchronized bypass.
Description: Sets the speed threshold to activate the bypass.
Note: When selecting p1260 = 3 and p1267.1 = 1, the bypass is automatically activated when this speed is reached.
Description: Sets the signal source for the control command to the bypass.
p1262[0...n] Bypass dead time / Bypass t_dead
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: CALC_MOD_REG Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 20.000 [s] 1.000 [s]
p1263 Debypass delay time / Debypass t_del
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 300.000 [s] 1.000 [s]
p1264 Bypass delay time / Bypass t_del
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 300.000 [s] 1.000 [s]
p1265 Bypass speed threshold / Bypass n_thresh
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: 3_1 Unit selection: p0505
Not for motor type: REL, RESM Scaling: p2000 Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 1480.00 [rpm]
p1266 BI: Bypass control command / Bypass command
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: RESM Scaling: - Expert list: 1
Min Max Factory setting
- - 0