SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
263
2 Parameters
2.2 List of parameters
Index: [0] = T0
[1] = T1
[2] = T2
Note: Limiting on:
If signals are output outside the permissible measuring range, the signal is limited to 4.98 V or to 0 V.
Limiting off:
If signals are output outside the permissible measuring range, this causes signal overflow. In the case of signal
overflow, the signal jumps from 0 V to 4.98 V or from 4.98 V to 0 V.
Description: Displays the scaling of the signal to be output.
A change in the output voltage by 1 volt corresponds to the value in this parameter. The units are determined by the
interconnected test signal.
Index: [0] = T0
[1] = T1
[2] = T2
Dependency: Refer to: p0771, r0772, r0774, p0777, p0778, p0779, p0780, p0783, p0784
Note: Example:
r0786[0] = 1500.0 and the measuring signal is r0063 (CO: Actual speed smoothed [rpm]).
A change of 1 V at the output of test socket T0 corresponds to 1500.0 [rpm].
Description: Sets the physical address to output signals via the test sockets.
Index: [0] = T0
[1] = T1
[2] = T2
Dependency: Changes only become effective if p0776 does not equal 99.
Refer to: p0789, r0790
Description: Sets the gain of a signal output of a physical address via test sockets.
Index: [0] = T0
[1] = T1
[2] = T2
Dependency: Changes only become effective if p0776 does not equal 99.
Refer to: p0788
r0786[0...2] Test socket scaling per volt / TestSktScale/Volt
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p0788[0...2] Test sockets physical address / Test skt PhyAddr
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 bin 1111 1111 1111 1111 1111 1111
1111 1111 bin
0000 bin
p0789[0...2] Test sockets physical address gain / TestSktPhyAddrGain
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-340.28235E36 340.28235E36 1.00000