SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
725
2 Parameters
2.2 List of parameters
Description: Sets the signal to be generated for the function generator.
Value: 1: Square-wave
2: Staircase
3: Delta
4: Binary noise - PRBS (Pseudo Random Binary Signal)
5: Sine-wave
Description: Sets the period of the signal to be generated for the function generator.
Dependency: Ineffective when p4820 = 4 (PRBS).
Description: Sets the pulse width for the signal to be generated for the function generator.
Dependency: Only effective when p4820 = 1 (square-wave).
Description: Sets the bandwidth for the signal to be generated for the function generator.
Dependency: Only effective when p4820 = 4 (PRBS).
Refer to: p4830
Refer to: A02041
p4820 Function generator signal shape / FG signal shape
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
1 5 1
p4821 Function generator period / FG period duration
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.00 [ms] 60000.00 [ms] 1000.00 [ms]
p4822 Function generator pulse width / FG pulse width
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.00 [ms] 60000.00 [ms] 500.00 [ms]
p4823 Function generator bandwidth / FG bandwidth
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.0025 [Hz] 16000.0000 [Hz] 4000.0000 [Hz]