2 Parameters
2.2 List of parameters
Description: Sets the signal source for control word S_STW1B of the Safety Control Channel.
Dependency: Refer to: p10203, r10251
Note: SCC: Safety Control Channel
Description: Display and BICO output for the diagnostics of control word S_STW1B of the safety control channel.
Dependency: Refer to: p10250
Note: SCC: Safety Control Channel
Description: Sets the telegram number for PROFIsafe.
Value: 0: No PROFIsafe telegram selected
30: PROFIsafe standard telegram 30, PZD-1/1
31: PROFIsafe standard telegram 31, PZD-2/2
901: PROFIsafe SIEMENS telegram 901, PZD-3/5
902: PROFIsafe SIEMENS telegram 902, PZD-3/6
Dependency: Refer to: p9611, p9811
Note: For p9601.3 = p9801.3 = 1 (PROFIsafe enabled), the following variants exist when parameterizing PROFIsafe
telegram 30:
- p9611 = p9811 = 998 and p60022 = 0
- p9611 = p9811 = 998 and p60022 = 30
- p9611 = p9811 = 30 and p60022 = 30
p10250 CI: SI Safety Control Channel control word S_STW1B / SCC S_STW1B
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r10251.8...12 CO/BO: SI Safety Control Channel control word S_STW1B diagnostics /
SCC S_STW1B diag
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
08 Extended functions test stop selection Selected Not selected 2837
09 Extended Functions referencing trigger Selected Not selected -
10 Extended Functions referencing reset Selected Not selected -
12 Extended Functions premature SOS after
STOP D
Selected Not selected -
p60022 PROFIsafe telegram selection / Ps telegram_sel
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 902 0