Siemens G130 - p0287[0...1] Ground fault monitoring threshold; Gnd flt threshold; r0289 CO: Maximum power unit output current; PU I_outp max; p0290 Power unit overload response; PU overld response

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
126 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the shutdown thresholds for the ground fault monitoring.
The setting is made as a percentage of the maximum current of the power unit (r0209).
Index: [0] = Reduced at the start of precharging
[1] = Regular
Dependency: Refer to: F30021
Note: The parameter only applies to booksize and chassis power units.
Deactivating the ground fault monitoring:
- Sequence: --> p0287[1] = 0 --> p0287[0] = 0
- irrespective of the firmware version of the power unit.
Sets the thresholds:
- the prerequisite is at least firmware version 2.2 of the power unit.
Description: Displays the actual maximum output current of the power unit taking into account derating factors.
Description: Sets the response to a thermal overload condition of the power unit.
The following quantities can result in a response to thermal overload:
- heat sink temperature (r0037[0]).
- chip temperature (r0037[1]).
- power unit overload I2t (r0036).
Possible measures to avoid thermal overload:
- reduce the output current limit r0289 and r0067 (for closed-loop speed/velocity or torque/force control) or the output
frequency (for U/f control) indirectly via the output current limit and the intervention of the current limiting controller).
- reduce the pulse frequency.
A reduction, if parameterized, is always realized after an appropriate alarm is output.
Value: 0: Reduce output current
1: No reduction shutdown when overload threshold is reached
2: Reduce the pulse frequency and output current
3: Reduce the pulse frequency
10: Automatic output current reduction
12: Automatic pulse frequency and output current reduction
13: Automatic pulse frequency reduction
p0287[0...1] Ground fault monitoring threshold / Gnd flt threshold
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [%] 100.0 [%] [0] 6.0 [%]
[1] 16.0 [%]
r0289 CO: Maximum power unit output current / PU I_outp max
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
p0290 Power unit overload response / PU overld response
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 8021
P-Group: Converter Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 13 0