4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1386 List Manual (LH2), 07/2016, A5E03263479A
F01060 CU: Internal error (parameter group not available)
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, TM150, VECTOR_G
Component: Control Unit (CU) Propagation: DRIVE
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The requested parameter group (IREG, NREG, ...) is not offered by this slave type.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy: Contact Technical Support.
F01061 CU: Internal error (application not known)
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, TM150, VECTOR_G
Component: Control Unit (CU) Propagation: DRIVE
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: An application that is not registered with TSM has attempted to register with registerSlaves().
The cause can be an unsuccessful TSM registration or an incorrect registration sequence. It is always necessary to
log in to the TSM before registerSlaves() can be used.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy: Contact Technical Support.
F01063 CU: Internal error (PDM)
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, TM150, VECTOR_G
Component: Control Unit (CU) Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: An internal software error has occurred.
Fault value (r0949, interpret hexadecimal):
Method ID.
Note:
Only for internal Siemens troubleshooting.
Remedy: Contact Technical Support.
A01064 (F) CU: Internal error (CRC)
Message value: -
Message class: Hardware/software error (1)
Drive object: All objects
Component: Control Unit (CU) Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: A checksum error (CRC error) has occurred in the Control Unit program memory
Remedy: - carry out a POWER ON (switch-off/switch-on) for all components.
- upgrade firmware to later version.
- contact Technical Support.