2 Parameters
2.2 List of parameters
SINAMICS G130/G150
560 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the scaling factor for torque utilization (r0033).
Description: Display and BICO output for the first status word of the monitoring functions.
Note: For bit 01, 02:
The threshold value is set in p2155 and the hysteresis in p2140.
For bit 03:
The hysteresis is set in p2150.
For bit 06:
The hysteresis is set in p2162.
For bit 07:
The threshold value is set in p2163 and the hysteresis is set in p2164.
For bit 13:
Only for internal Siemens use.
Description: Display and BICO output for the second status word of the monitoring functions.
p2196[0...n] Torque utilization scaling / M_util scal
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 1000.00 [%] 100.00 [%]
r2197.1...13 CO/BO: Status word monitoring 1 / ZSW monitor 1
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2534
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
01 |n_act| <= speed threshold value 2 p2155 Yes No 8010
02 |n_act| > speed threshold value 2 p2155 Yes No 8010
03 n_act >= 0 Yes No 8011
06 |n_act| > n_max Yes No 8010
07 Speed setp - act val deviation in tolerance
t_off
Yes No 8011
13 |n_act| > n_max (F07901) Yes No -
r2198.4...12 CO/BO: Status word monitoring 2 / ZSW monitor 2
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2536
P-Group: Messages Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
04 |n_set| < p2161 Yes No 8011
05 n_set > 0 Yes No 8011
06 Motor blocked Yes No 8012
07 Motor stalled Yes No 8012
10 |M_set| < torque threshold value 1 Yes No 8012
11 Load in the alarm range Yes No 8013
12 Load in the fault range Yes No 8013