2 Parameters
2.2 List of parameters
Note: When the ground fault monitoring initiates a fault for overlapping synchronizing the threshold value p0287[1] for the
Motor Module and the associated infeed must be appropriately increased (e.g. p0287[1] = 100 %).
For p3800 = 1, the following applies:
The INTERNAL voltage actual values are used for synchronization. The effects that a (sine-wave) filter - that is
connected between the Motor Module and motor - has on the voltage actual values are taken into account
(theoretically) by appropriately selecting p0230.
VSM: Voltage Sensing Module
Description: Sets the drive object number of the VSM used for the line-drive synchronization.
Dependency: Refer to: p3800, p3802
Notice: The current controller sampling time p0115[0] of the drive object with the VSM used for synchronization must be
identical to the current controller sampling time of the drive of the drive used to perform line synchronization.
Note: VSM: Voltage Sensing Module
The setting p3801 = 1 is always possible (no VSM selected).
If the VSM is assigned subsequently to a Motor Module, its drive object number must be entered in p3801.
The line voltage is always measured using the first VSM (p0151[0]).
Description: Sets the signal source to switch in/switch out for the line-drive synchronization.
BI: p3802 = 1 signal:
The line-drive synchronization is switched in.
Dependency: Refer to: p3800, p3801
Description: Displays the control word for the line-drive synchronization.
Note: For bit 00:
For a 1 signal, p3800 > 0 is set.
p3801[0...n] Sync-line-drive drive object number / Sync DO_no
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 62 1
p3802[0...n] BI: Sync-line-drive enable / Sync enable
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 7020
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r3803.0 CO/BO: Sync-line-drive control word / Sync STW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Sync-line-drive selected Yes No -