2 Parameters
2.2 List of parameters
SINAMICS G130/G150
462 List Manual (LH2), 07/2016, A5E03263479A
Description: Displays the effective modulator mode.
Value: 1: Flat top modulation (FLB)
2: Space vector modulation (SVM)
3: Edge modulation from 28 Hz; 23:3
4: Edge modulation from 28 Hz; 19:1
5: Edge modulation from 60 Hz; 17:3
6: Edge modulation from 60 Hz; 17:1
7: Edge modulation from 100 Hz; 9:2
8: Edge modulation from 100 Hz; 9:1
9: Optimized pulse pattern
Description: Sets the configuration for the modulator.
Dependency: If bit 2 is set from 1 to 0, p1811 = 0 is set.
Notice: Bit 1 = 0 can only be set under a pulse inhibit and for r0192.14 = 1.
Bit 2 can only be set to 1 subject to the following prerequisites:
- Pulse inhibit
- r0192.16 = 1
- p1800 < 2 x 1000/p0115[0]
r1809 CO: Modulator mode actual / Modulator mode act
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 9 -
p1810 Modulator configuration / Modulator config
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Modulation Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0010 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Avg value filter for V_lim (only for
Vdc_comp in modulator)
Yes No -
01 DC link voltage compensation in the current
control
Yes No -
02 Wobbulation activated Yes No -
03 Current measurement oversampling
selected
Yes No -
08 Pulse frequency reduction (speed
dependent) stage 1
Yes No -
09 Pulse frequency reduction (speed
dependent) stage 2
Yes No -
10 Activate pulse-locking/pulse-dropping
function
Pulse-Dropping Pulse-Locking -
12 Pulse freq. can be asynchronously set to
curr. ctrl clock cycle
Yes No -
13 Pulse freq. reduction before optimized pulse
patterns for 500 µs
Yes No -
14 Deactivate maximum angular difference
adaptation
Yes No -
15 Increase overmodulation range Yes No -