List Manual (LH2), 07/2016, A5E03263479A
323
2 Parameters
2.2 List of parameters
Description: Display and BICO output for the skip bands.
Dependency: Refer to: r1170
Note: For bit 00:
With the bit set, the setpoint speed is within the skip band after the ramp-function generator (r1170).
The signal can be used to switch over the drive data set (DDS).
Description: Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency: Refer to: p1091, p1092, p1093, p1094
Note: The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
Description: Sets the signal source for lowest possible motor speed.
Dependency: Refer to: p1080
Notice: The effective minimum speed is formed from p1080 and p1106.
r1099.0 CO/BO: Skip band status word / Skip band ZSW
VECTOR_G Can be changed: - alculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 r1170 within the skip band Yes No 3050
p1101[0...n] Skip speed bandwidth / n_skip bandwidth
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 3050
P-Group: Setpoints Unit group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
0.000 [rpm] 210000.000 [rpm] 0.000 [rpm]
p1106[0...n] CI: Minimum speed signal source / n_min s_src
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3050
P-Group: Setpoints Unit group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0