SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
37
2 Parameters
2.2 List of parameters
Description: Operating display for Terminal Module 54F (TM54F).
Value: 0: Module in cyclic operation
40: Module not in cyclic operation
50: Alarm
60: Fault
70: Initialization
120: Module deactivated
200: Wait for booting/partial booting
250: Device signals a topology error
Description: Operating display for encoder drive object.
Value: 0: Encoder in cyclic operation
35: Carry out first commissioning (p0010)
45: Remove fault cause, acknowledge fault
46: Exit commissioning mode (p0009, p0010)
60: Encoder deactivated
200: Wait for booting/partial booting
250: Device signals a topology error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
Description: Operating display for the DRIVE-CLiQ Hub Module.
Value: 0: Module in cyclic operation
40: Module not in cyclic operation
50: Alarm
60: Fault
70: Initialization
120: Module deactivated
200: Wait for booting/partial booting
250: Device signals a topology error
Notice: For several missing enable signals, the corresponding value with the highest number is displayed.
r0002 TM54F operating display / TM54F op_display
TM54F_MA,
TM54F_SL
Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 250 -
r0002 Encoder DO operating display / Enc DO op_display
ENC Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 250 -
r0002 DRIVE-CLiQ Hub Module operating display / Hub op_display
HUB Can be changed: - Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 250 -