2 Parameters
2.2 List of parameters
SINAMICS G130/G150
664 List Manual (LH2), 07/2016, A5E03263479A
Description: Sets the setpoint for the input signals in the simulation mode of the digital inputs of the Terminal Board 30 (TB30).
Dependency: The simulation of a digital input is selected using p4095.
Refer to: p4095
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Description: Sets the simulation mode for the analog inputs of Terminal Module 31 (TM31).
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description: Sets the simulation mode for the analog inputs of the Terminal Board 30 (TB30).
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency: The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
p4096 TB30 digital inputs simulation mode setpoint / TB30 DI sim setpt
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 9099, 9100
P-Group: Commands Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X481.1) High Low -
01 DI 1 (X481.2) High Low -
02 DI 2 (X481.3) High Low -
03 DI 3 (X481.4) High Low -
p4097[0...1] TM31 analog inputs simulation mode / TM31 AI sim_mode
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4097[0...1] TB30 analog inputs simulation mode / TB30 AI sim_mode
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0