4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1884 List Manual (LH2), 07/2016, A5E03263479A
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[2] = 1, 4), the following applies:
- if r4101[2] > 1650 ohms, the temperature r4105[2] = 250 °C
- if r4101[2] <= 1650 ohms, the temperature r4105[2] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy: Allow the temperature sensor to cool down to below p4102[4] - hysteresis (5 K, for TM150, can be set using
p4118[2]).
See also: p4102
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE
A35214 (F, N) TM: Temperature alarm threshold channel 3 exceeded
Message value: %1
Message class: External measured value / signal state outside the permissible range (16)
Drive object: B_INF, TM120, TM150, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: NONE
Acknowledge: NONE
Cause: The temperature measured using the temperature sensing of the Terminal Module (TM) (r4105[3]) has exceeded the
threshold value to initiate this alarm (p4102[6]).
Note:
For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[3] = 1, 4), the following applies:
- if r4101[3] > 1650 ohms, the temperature r4105[3] = 250 °C
- if r4101[3] <= 1650 ohms, the temperature r4105[3] = -50 °C
Alarm value (r2124, interpret decimal):
Temperature actual value at the time of initiation [0.1 °C].
Remedy: Allow the temperature sensor to cool down to below p4102[6] - hysteresis (5 K, for TM150, can be set using
p4118[3]).
See also: p4102
Reaction upon F: NONE
Acknowl. upon F: IMMEDIATELY (POWER ON)
Reaction upon N: NONE
Acknowl. upon N: NONE
F35220 (N, A) TM: Frequency limit reached for signal output
Message value: -
Message class: Application/technological function faulted (17)
Drive object: B_INF, TM31, VECTOR_G
Component: Terminal Module (TM) Propagation: BICO
Reaction: Vector: OFF1 (NONE, OFF2, OFF3)
Infeed: OFF1 (NONE, OFF2)
Acknowledge: IMMEDIATELY (POWER ON)
Cause: The signals output from the Terminal Module 41 (TM41) for tracks A/B have reached the limit frequency. The output
signals are no longer in synchronism with the specified setpoint.
SIMOTION (p4400 = 0) operating mode:
- if the TM41 has been configured as the technology project, this fault is also output in response to short-circuited A/B
signals in X520.
SINAMICS (p4400 = 1) operating mode:
- the fine resolution of TM41 in p0418 does not match that of the connector input that was interconnected at p4420
- the encoder position actual value r0479 interconnected at connector input p4420 has an excessively high actual
speed
- the output signals correspond to a speed, which is greater than the maximum speed (r1082 of TM41).