363
2 Parameters
2.2 List of parameters
Description: Sets the configuration for the "flying restart function" function.
Note: ASM: Induction motor
PMSM: permanent-magnet synchronous motor
For bit 00:
This bit is equivalent to p1780 bit 1.
For bit 01:
This bit should only be set when required for large drives.
Description: Sets the maximum search frequency for a flying restart in an inhibited setpoint direction (p1110, p1111).
Note: The parameter has no effect for an operating mode, which only searches in the setpoint direction (p1200 > 3).
Description: In the simulation mode, the closed-loop control or U/f control can be operated without motor.
The simulation mode is used to test the power unit. Even though the DC link voltage is missing, the pulses are
enabled when switching on. The DC link precharging is bypassed and the undervoltage detection is disabled.
Closed-loop speed control with an encoder is possible if the torque setpoint (r0079) is used in order to operate a
second drive in the closed-loop torque controlled mode.
Value: 0: OFF
1: ON
Dependency: The following functions are deactivated in the simulation mode:
- motor data identification routine
- motor data identification routine, rotating without encoder
- pole position identification
p1270[0...n] Flying restart configuration / Fly restart config
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Unit group: - Unit selection: -
Not for motor type: PMSM, SESM, REL,
RESM
Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fast flying restart with voltage model for
induction motor
Yes No -
01 PLL expansion for fast flying restart w/
voltage model for ASM
Yes No -
12 Siemens internal Yes No -
13 Siemens internal 1 0 -
14 Siemens internal 1 0 -
15 Siemens internal 1 0 -
p1271[0...n] Flying restart maximum frequency for the inhibited direction / FlyRes f_max dir
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [Hz] 650 [Hz] 0 [Hz]
p1272 Simulation mode / Simulation mode
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Functions Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0