SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
883
2 Parameters
2.2 List of parameters
Description: Displays the MAC address for the onboard PROFINET interface on the Control Unit.
Description: Displays the state of the cyclic PROFINET connections.
Value: 0: Interrupted
1: Not connected
2: Connection starts to be established
3: Module information expected
4: Module information received
5: Module address expected
6: Module address received
7: Parameterization data expected
8: Parameterization data received
9: Evaluate parameterization data
10: Connection being established completion expected
11: Configured controller RUN expected
12: Configured controller STOP
13: Configured controller RUN
Index: [0] = Controller 1
[1] = Controller 2
Dependency: Refer to: p8929, r8961, r8962
Note: For two connections (Shared Device or system redundancy) the display in the index depends on the sequence in
which the connections are established.
The IP addresses of controllers 1 and 2 are displayed in r8961 and r8962.
The following states are displayed for system redundancy:
Primary controller: r8936[x] = 13
Backup controller: r8936[x] = 11
If value = 10:
If the connection remains in this state, then when using PROFINET IRT the following can apply:
- topology error (incorrect port assignment).
- synchronization missing.
Description: Display to diagnose the cyclic PROFINET connections.
Index: [0] = Number of cyclic connections
[1] = Number of send subslots of all connections
r8935[0...5] PN MAC address / PN MAC addr
CU_G130_PN,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex 00FF hex -
r8936[0...1] PN cyclic connection state / PN cyc conn state
CU_G130_PN,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 13 -
r8937[0...5] PN diagnostics / PN diag
CU_G130_PN,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -