Siemens G130 - F35052 (A) TM54 F: Internal hardware error; F35053 TM54 F: Temperature fault threshold exceeded; A35054 TM54 F: Temperature alarm threshold exceeded

Siemens G130
1976 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1876 List Manual (LH2), 07/2016, A5E03263479A
Remedy: Carry out the following steps on the TM54F:
- check the specified parameters for incorrect parameterization.
- activate the safety commissioning mode (p0010 = 95).
- start the copy function for SI parameters (p9700 = 57 hex).
- acknowledge complete data change (p9701 = AC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0977 = 1).
- carry out safe acknowledgment (p10006).
For an internal software error (aaaa > 0):
- For TM54F, upgrade the firmware to a later version.
- contact Technical Support.
- replace the TM54F.
F35052 (A) TM54F: Internal hardware error
Message value: %1
Message class: Hardware/software error (1)
Drive object: B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY (POWER ON)
Cause: An internal software/hardware error has been detected on the Terminal Module 54F (TM54F).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - check the electrical cabinet design and cable routing for EMC compliance
- upgrade TM54F firmware to more recent version.
- contact Technical Support.
- replace the TM54F.
Reaction upon A: NONE
Acknowl. upon A: NONE
F35053 TM54F: Temperature fault threshold exceeded
Message value: %1
Message class: Overtemperature of the electronic components (6)
Drive object: B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: GLOBAL
Reaction: NONE
Acknowledge: IMMEDIATELY
Cause: The temperature measured using the temperature sensing on the TM54F has exceeded the threshold value to
initiate this fault.
As fault response fail-safe input terminal signals are transferred to the motion monitoring functions.
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - allow the TM54F to cool down.
- carry out safe acknowledgment (p10006).
A35054 TM54F: Temperature alarm threshold exceeded
Message value: %1
Message class: Overtemperature of the electronic components (6)
Drive object: B_INF, TM54F_MA, TM54F_SL, VECTOR_G
Component: Terminal Module (TM) Propagation: GLOBAL
Reaction: NONE
Acknowledge: NONE
Cause: The temperature measured using the temperature sensing on the TM54F has exceeded the threshold value to
initiate this alarm.
Remedy: - allow the TM54F to cool down.
- carry out safe acknowledgment (p10006).