List Manual (LH2), 07/2016, A5E03263479A
141
2 Parameters
2.2 List of parameters
For 1PQ8 motors, p0335 should be set to 5 as these motors are force-ventilated motors.
The setting p0335 = 128 applies for 1LA7 motors, frame size 56 (these are operated without a fan).
Description: Displays the rated frequency of the motor.
For p0310 > 0, this value is displayed.
Dependency: Refer to: p0311, p0314
Note: For p0310 = 0 or for synchronous motors, the rated motor frequency r0336 is calculated from the rated speed and the
pole pair number.
For p0310 > 0, this value is displayed (not for synchronous motors).
Description: Displays the rated EMF of the motor.
Note: EMF: Electromotive force
Description: Displays the rated motor voltage.
Note: For induction motors (p0300 = 1xx) the parameter is set to p0304.
For synchronous motors, parameter r0339 = p0304 is displayed. If p0304 = 0, then r0339 is calculated from p0305
and p0316.
Description: Setting to automatically calculate motor parameters and U/f open-loop and closed-loop control parameters from the
rating plate data.
Value: 0: No calculation
1: Complete calculation
2: Calculation of equivalent circuit diagram parameters
3: Calculation of closed-loop control parameters
4: Calculation of controller parameters
5: Calculation of technological limits and threshold values
r0336[0...n] Actual rated motor frequency / Mot f_rated act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [Hz] - [Hz] - [Hz]
r0337[0...n] Rated motor EMF / Mot EMF_rated
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: REL, RESM Scaling: - Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
r0339[0...n] Rated motor voltage / Mot U_rated
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p0340[0...n] Automatic calculation motor/control parameters / Calc auto par
VECTOR_G Can be changed: C2(3), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Motor Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 5 0