2 Parameters
2.2 List of parameters
SINAMICS G130/G150
262 List Manual (LH2), 07/2016, A5E03263479A
Description: The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the x coordinate (percentage) of the second point on the characteristic.
Index: [0] = T0
[1] = T1
[2] = T2
Dependency: Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0780, r0786
Note: The value 100.00 % corresponds to 4.98 V.
Description: The scaling characteristic for the test sockets is defined using two points.
This parameter specifies the y coordinate (output voltage) of the second point on the characteristic.
Index: [0] = T0
[1] = T1
[2] = T2
Dependency: Can only be set when p0776 = 99.
Refer to: p0777, p0778, p0779, r0786
Description: Sets an additional offset for the test sockets.
Index: [0] = T0
[1] = T1
[2] = T2
Description: Sets the limit for a signal to be output via test sockets.
Value: 0: Limiting off
1: Limiting on
p0779[0...2] Test socket characteristic value x2 / Test skt char x2
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-100000.00 [%] 427.9E9 [%] 100.00 [%]
p0780[0...2] Test socket characteristic value y2 / Test skt char y2
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [V] 4.98 [V] 4.98 [V]
p0783[0...2] Test sockets offset / Test skt offset
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-4.98 [V] 4.98 [V] 0.00 [V]
p0784[0...2] Test socket limit on/off / TestSktLim on/off
CU_G130_PN,
CU_G150_PN,
CU_G130_DP,
CU_G150_DP
Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 8134
P-Group: Terminals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0