SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
289
2 Parameters
2.2 List of parameters
Description: Display and BICO output for the status word of the sequence control of the infeed unit.
Note: For bits 00, 01, 02, 04, 06, 09:
For PROFIdrive, these signals are used for status word 1.
Description: Displays the status word for sequence control on the encoder drive object.
Note: For PROFIdrive, this signal is used for status word ZSW2_ENC.
Description: Displays or sets the PROFIBUS address for PROFIBUS interface on the Control Unit.
The address can be set as follows:
1) Using the address switch on the Control Unit.
--> p0918 can then only be read and displays the selected address.
--> A change only becomes effective after a POWER ON.
2) Using p0918
--> Only if the address 00 hex, 7F hex, 80 hex, or FF hex has been set using the address switch.
--> The address is saved in a non-volatile fashion using the function "copy from RAM to ROM".
--> A change only becomes effective after a POWER ON.
Note: Permissible PROFIBUS addresses: 1 ... 126 (01 hex ... 7E hex)
Address 126 is used for commissioning.
Every PROFIBUS address change only becomes effective after a POWER ON.
The parameter is not influenced by setting the factory setting.
r0899.0...12 CO/BO: Status word sequence control infeed / ZSW seq_ctrl INF
B_INF Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8726
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Ready for switching on Yes No -
01 Ready Yes No -
02 Operation enabled Yes No -
04 No OFF2 active OFF2 inactive OFF2 active -
06 Switching-on inhibited Yes No -
08 Switching-on operation active Yes No -
09 Control request Yes No -
11 Precharging complete Yes No -
12 Line contactor closed Yes No -
r0899.7...9 CO/BO: Status word sequence control encoder DO / ZSW seq_ctrl encDO
ENC Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
07 Drive ready Yes No -
09 Control request Yes No -
p0918 PROFIBUS address / PB address
CU_G130_DP,
CU_G150_DP
Can be changed: T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 2401, 2410
P-Group: Communications Unit group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 126 126