4 Faults and alarms
4.2 List of faults and alarms
SINAMICS G130/G150
1938 List Manual (LH2), 07/2016, A5E03263479A
A50007 (F) COMM BOARD: Alarm 7
Message value: Info. 1: %1, info. 2: %2
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 SINAMICS Link:
A send telegram word is greater than possible in the project.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = drive object number from p8871
Info. 2 (decimal) = index from p8871
See also: p8811 (SINAMICS Link project selection), p8871 (SINAMICS Link PZD send word)
Remedy: In the case of CBE20 SINAMICS Link:
Correct the parameter assignment.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50008 (F) COMM BOARD: Alarm 8
Message value: Info. 1: %1, info. 2: %2
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: CBE20 SINAMICS Link:
A receive telegram word is greater than possible in the project.
Alarm value (r2124, interpret hexadecimal):
yyyyxxxx hex: yyyy = info. 1, xxxx = info. 2
Info. 1 (decimal) = drive object number from p8870
Info. 2 (decimal) = index from p8870
See also: p8811 (SINAMICS Link project selection), p8870 (SINAMICS Link PZD receive word)
Remedy: In the case of CBE20 SINAMICS Link:
Correct the parameter assignment.
Reaction upon F: Vector: NONE (OFF1, OFF2, OFF3)
Infeed: NONE (OFF1, OFF2)
Acknowl. upon F: IMMEDIATELY
A50010 (F) PNCOMM BOARD: Consistency error affecting adjustable parameters
Message value: %1
Message class: Communication error to the higher-level control system (9)
Drive object: All objects
Component: None Propagation: LOCAL
Reaction: NONE
Acknowledge: NONE
Cause: A consistency error was detected when activating the configuration (p8945) for the Communication Board Ethernet
20 (CBE20).
Alarm value (r2124, interpret decimal):
0: general consistency error
1: error in the IP configuration (IP address, subnet mask or standard gateway).
2: Error in the station names.
3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists.
4: a cyclic PROFINET connection is not possible as DHCP is activated.